Skip to main content
skill CX Codex

hvac-design — Claude Code skill: HVAC design and setup

hvac-design is a Claude Code skill for calculating HVAC loads, selecting equipment, and assessing energy use. It supports building heating, ventilation, and air-conditioning design under ASHRAE standards.

MIT 5 installs ★ 1,931 updated 2026-09-16

Install into Claude Code · Skills CLI (Vercel) All methods and platforms ↓
npx skills add a5c-ai/babysitter --skill hvac-design -a claude-code
Open on GitHub

What hvac-design does

hvac-design calculates heating and cooling loads, works through psychrometric analysis, and helps select AHUs, chillers, and boilers. It also covers duct and pipe sizing, indoor air quality checks, and energy analysis against ASHRAE 90.1.

The calculation inputs include building location and type, floor area, number of floors, indoor conditions, and internal loads. Results can include peak loads, ventilation airflow, equipment specifications, and annual energy figures. Ventilation analysis uses ASHRAE 62.1.

What it helps with

  • calculate peak heating and cooling loads for a building
  • select an AHU, chiller, or boiler from design loads
  • size ductwork and piping systems
  • estimate annual building energy use

Example prompts for the agent

  • Calculate heating and cooling loads for this office building using its location and design conditions.
  • Select an AHU and chiller for the calculated loads.
  • Assess annual energy use and check the design against ASHRAE 90.1.

How to install hvac-design

1Skills CLI (Vercel)

npx skills add a5c-ai/babysitter --skill hvac-design -a claude-code

2Manually: put the files in place

~/.claude/skills/hvac-design/SKILL.md

Copy the whole skill folder; for one project use .claude/skills/hvac-design/

Step by step, with commands for each platform: How to install skills in Claude Code: five ways

Questions about hvac-design

How do I install hvac-design in Claude Code?

Run npx skills add a5c-ai/babysitter --skill hvac-design -a claude-code. The skill file is located at ~/.claude/skills/hvac-design/SKILL.md.

What does hvac-design do?

It supports HVAC design by calculating building loads, helping choose equipment, and analyzing energy performance against ASHRAE standards.

What information does hvac-design need for a building calculation?

Inputs include the building location, type, floor area, floor count, indoor temperature and humidity conditions, plus occupancy, lighting, and equipment loads.

Source text

SKILL.md · MIT
---
name: hvac-design
description: Skill for HVAC system design and analysis per ASHRAE standards including load calculations, equipment selection, and energy efficiency analysis
allowed-tools:
  - Read
  - Write
  - Glob
  - Grep
  - Bash
metadata:
  specialization: mechanical-engineering
  domain: science
  category: thermal-fluid-analysis
  priority: high
  phase: 6
  tools-libraries:
    - Carrier HAP
    - Trane TRACE
    - EnergyPlus
    - eQUEST
graph:
  domains: [domain:mechanical-engineering]
  skillAreas: [skill-area:physics-simulation, skill-area:mathematical-reasoning, skill-area:motion-planning]
  roles: [role:systems-integration-engineer, role:research-engineer]
---

# HVAC System Design Skill

## Purpose

The HVAC System Design skill provides comprehensive capabilities for heating, ventilation, and air conditioning system design according to ASHRAE standards, enabling systematic load calculations, equipment selection, ductwork design, and energy efficiency analysis for commercial and industrial buildings.

## Capabilities

- Heating and cooling load calculations
- Psychrometric analysis and chart calculations
- Equipment selection (AHU, chillers, boilers)
- Duct and piping system sizing
- Energy efficiency analysis (ASHRAE 90.1)
- Indoor air quality assessment (ASHRAE 62.1)
- System simulation and optimization
- Control system specification

## Usage Guidelines

### Load Calculations

#### Cooling Load Components

1. **External Loads**
   - Solar radiation through windows (SHGC consideration)
   - Conduction through envelope (walls, roof, floor)
   - Infiltration and ventilation air

2. **Internal Loads**
   - People: 250 Btu/h sensible, 200 Btu/h latent (typical office)
   - Lighting: Use installed wattage with diversity
   - Equipment: Plug loads with usage factors

3. **Calculation Methods**
   - CLTD/CLF method: Manual calculations
   - RTS (Radiant Time Series): More accurate
   - Heat Balance Method: Full simulation

#### Heating Load

1. **Design Conditions**
   - Use ASHRAE 99.6% or 99% design temperature
   - No solar credit for heating design
   - Full infiltration at design conditions

2. **Load Components**
   - Envelope conduction (U × A × ΔT)
   - Infiltration/ventilation (1.08 × CFM × ΔT)
   - No internal gains credited

### Psychrometric Analysis

1. **Key Properties**
   - Dry-bulb and wet-bulb temperatures
   - Relative humidity and humidity ratio
   - Enthalpy and specific volume
   - Dew point temperature

2. **Process Calculations**
   | Process | Constant Property |
   |---------|------------------|
   | Sensible heating/cooling | Humidity ratio |
   | Humidification | Enthalpy (adiabatic) |
   | Dehumidification | Saturation curve |
   | Mixing | Mass-weighted average |

3. **Coil Processes**
   ```
   Sensible Heat Ratio (SHR) = Qs / Qt

   Bypass Factor (BF) = (T_leaving - T_ADP) / (T_entering - T_ADP)
   ```

### Equipment Selection

#### Air Handling Units

1. **Coil Sizing**
   - Entering/leaving air conditions
   - Water temperatures (chilled water: 44/54°F typical)
   - Face velocity: 400-550 fpm

2. **Fan Selection**
   - Total static pressure requirements
   - Fan efficiency and motor sizing
   - Variable speed considerations

#### Chillers

1. **Types and Selection**
   - Reciprocating: < 200 tons
   - Scroll: 20-400 tons
   - Screw: 100-1500 tons
   - Centrifugal: > 300 tons

2. **Efficiency Metrics**
   - COP (Coefficient of Performance)
   - kW/ton: 0.5-0.8 typical range
   - IPLV: Part-load efficiency

### Duct Design

1. **Sizing Methods**
   - Equal friction: Constant pressure drop per 100 ft
   - Static regain: Constant velocity pressure
   - Velocity method: Noise-controlled

2. **Pressure Drop**
   - Typical systems: 0.08-0.1 in.w.g./100 ft
   - Low velocity: < 0.08 in.w.g./100 ft
   - High velocity: > 0.1 in.w.g./100 ft

3. **Fitting Losses**
   - Express as equivalent length or C coefficient
   - Use ASHRAE duct fitting database

### Energy Efficiency

1. **ASHRAE 90.1 Compliance**
   - Envelope requirements (U-values, SHGC)
   - HVAC efficiency minimums
   - Lighting power density limits
   - Energy cost budget method

2. **Energy Conservation Measures**
   - Economizer operation
   - Heat recovery
   - Variable speed drives
   - Demand-controlled ventilation

## Process Integration

- ME-013: HVAC System Design

## Input Schema

```json
{
  "building": {
    "location": "string",
    "type": "office|retail|healthcare|industrial",
    "gross_area": "number (ft2)",
    "floors": "number"
  },
  "design_criteria": {
    "indoor_summer": {
      "temp": "number (F)",
      "rh": "number (%)"
    },
    "indoor_winter": {
      "temp": "number (F)"
    },
    "ventilation_standard": "ASHRAE 62.1|local code"
  },
  "internal_loads": {
    "occupancy": "number (people)",
    "lighting": "number (W/ft2)",
    "equipment": "number (W/ft2)"
  }
}
```

## Output Schema

```json
{
  "loads": {
    "peak_cooling": "number (tons)",
    "peak_heating": "number (MBH)",
    "ventilation": "number (CFM)"
  },
  "equipment": {
    "ahu": [{
      "designation": "string",
      "supply_cfm": "number",
      "cooling_tons": "number",
      "heating_mbh": "number"
    }],
    "chiller": {
      "type": "string",
      "capacity": "number (tons)",
      "efficiency": "number (kW/ton)"
    },
    "boiler": {
      "type": "string",
      "capacity": "number (MBH)",
      "efficiency": "number (%)"
    }
  },
  "energy_analysis": {
    "annual_cooling": "number (kWh)",
    "annual_heating": "number (therms)",
    "eui": "number (kBtu/ft2/yr)"
  }
}
```

## Best Practices

1. Use ASHRAE weather data for design conditions
2. Apply appropriate safety factors (10-15% typical)
3. Consider zone diversity for central equipment
4. Verify ventilation rates meet ASHRAE 62.1
5. Model energy performance before finalizing design
6. Coordinate with architectural and structural disciplines

## Integration Points

- Connects with CFD Analysis for airflow modeling
- Feeds into Thermal Analysis for component design
- Supports Building Energy Simulation for annual performance
- Integrates with Control System Design for automation

© a5c-ai · MIT · a5c-ai/babysitter

Similar skills

All skills for Science and research →

From the same set37

The whole set →
crm-integration Skill for deep CRM integration: query and update contacts, log interactions, sync health scores, trigger workflows. Works with Salesforce, HubSpot, Microsoft Dynamics to automate customer data workflows. CX Codex +1 18installs policy-management policy-management runs the corporate policy cycle: drafting, versions, approvals, distribution, attestations and the review schedule. CX Codex +1 3installs seo seo configures meta tags and sitemaps directly in project files. Useful when preparing web applications for search indexing. CX Codex +1 3installs logistics-kpi-tracker The logistics-kpi-tracker skill measures delivery and cost metrics against targets, compares periods, and surfaces possible causes of gaps. Use it to review performance by channel or region. CX Codex +1 2installs seo-tools seo-tools wires Semrush, Ahrefs, Google Search Console and Moz into your agent, so keyword, ranking and backlink data land in one report. CX Codex +1 2installs godot-3d godot-3d guides your AI coding agent through Godot Engine 3D setup. It covers PBR materials, WorldEnvironment nodes, lighting, and camera handling. CX Codex +1 2installs sensor-fusion sensor-fusion guides AI assistants in configuring Kalman filters, robot_localization, and multi-sensor pipelines merging IMU, odometry, and GPS data. CX Codex +1 1installs Network Protocol Analysis Skill The Network Protocol Analysis Skill skill captures and examines network traffic, crafts packets, and fuzzes protocols. Use it for protocol reverse engineering and security research. CX Codex +1 1installs

Project sponsors

Companies that keep this analytics open